user.png Register      arrow.png Sign in

Thailand-icon.png United-Kingdom-icon.png

5725.png

5725

Programmable frequency indicator

  • Measures NPN, PNP, Contact, NAMUR, S0, Tacho and TTL sensors
  • Programmable frequency input span of 0.001 Hz to 50 kHz
  • The 5725D has two SPDT relays and one analog output
  • Easy to read 4-digit, 14-segment LED display with scrolling help text
  • Universally powered by 21.5…253 VAC or 19.2… 300 VDC

Manuals : pdf-icon.png

Data sheet : pdf-icon.png

  • Overview

  • Technical details

  •  

    Application

    • The 5725 measures, scales, and displays frequency signals found in many process speed and flow rate applications.
    • The indicator can measure the period of the frequency, useful for displaying the elapsed time between events.
    • The 5725D has two SPDT setpoint contacts and a 0/4...20 mA output for process control.
    • The installed display provides IP65 environmental sealing, and additional protection is provided by the optional 8335 splash proof cover.

    Technical characteristics

    • 4-digit display with 13.8 mm high, 14-segment LED digits and adjustable decimal point.
    • Indicator is scalable from -1999 to 9999.
    • Scrolling help text makes programming easy.
    • Customizable trigger levels allow measurement of nearly any pulse sensor.
    • Built-in excitation source for measuring NPN, PNP, NAMUR and S0 sensors.
    • Fast response time of 1 cycle + 100 ms, and excellent accuracy of better than 0.05% of selected range.
    • The analog output current on the 5725D can be dampened from 0.1 to 60 seconds, and can handle up to 800 Ohms loop load.
    • The 5725 meets NAMUR NE21 recommendations for high performance in harsh EMC environments.
    • High 2.3 kVAC galvanic isolation, and an excellent signal/noise ratio of > 60dB.

    Mounting / installation / programming

    • Easy to mount 1/8 DIN (48x96 mm) panel meter with IP65 (type 4X) sealing.
    • Approved for marine applications.
    • Fully push-button programmable.
    • Password-protected.
  •  

    Environmental Conditions

    Specifications range -20°C to +60°C
    Storage temperature -40°C to +85°C
    Calibration temperature 20...28°C
    Relative humidity < 95% RH (non-cond.)
    Protection degree IP20
    Protection degree (mounted in panel) IP65 / Type 4X, UL50E
    Installation in Pollution degree 2 & measurement / overvoltage cat. II

    Mechanical specifications

    Dimensions (HxWxD) 48 x 96 x 120 mm
    Cut out dimensions 44.5 x 91.5 mm
    Weight approx. 230 g
    Wire size, pin 11-12 & 41-44, max. 1 x 1.5 mm2/ AWG 30...16 stranded wire
    Wire size, others, max. 1 x 2.5 mm2/ AWG 30...12 stranded wire
    Terminal connection Spring-cage
    Vibration IEC 60068-2-6 : 2007
    Vibration: 2...25 Hz ±1.6 mm
    Vibration: 25...100 Hz ±4 g

    Common specifications

    Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
    Max. power consumption < 2.8 W (5725A) < 3.6 W (5725D)
    Isolation voltage, test / working 2.3 kVAC / 250 VAC
    Signal / noise ratio > 60 dB
    Accuracy Better than 0.05% of selected range
    Response time (0...90%, 100...10%) < 1 period + 100 ms
    EMC immunity influence < ±0.5% of span
    Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span

    Input specifications

    Frequency range, f/I conversion function 0.001 Hz to 50 kHz
    Low cut-off frequency 0.0009 Hz (default value)
    Max. frequency, with input filter ON 50 Hz
    Time range, period time function 999.9 s to 20 μs
    Low cut off period time (time-out) 1111 s
    Min. period time with input filter ON 20 ms
    Input types NAMUR acc. to EN 60947-5-6 Tacho
    NPN / PNP
    TTL
    S0 acc. to DIN 43864
    Special voltage
    Special current

    Output specifications

    Display readout -1999...9999 (4 digits)
    Decimal point Programmable
    Digit height 13.8 mm
    Display updating. 2.2 times / s
    Input outside input range is indicated by Explanatory text
    Programmable current ranges 0...20 / 4...20 / 20...0 and 20...4 mA
    Load (max.) 20 mA/800 Ω/16 VDC
    Load stability, current output ≤0.01% of span / 100 Ω
    Current limit ≤ 28 mA
    Sensor error indication, current output 0 / 3.5 / 23 mA / none
    Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA
    Output limitation, on 0...20 and 20...0 mA signals 0...20.5 mA
    Relay output: Relay functions Setpoint
    Hysteresis, in % / display counts 0...100% / 0...9999
    ON and OFF delay 0...3600 s
    Power On delay 0...60 s
    Sensor error reaction Break / Make / Hold
    Max. voltage 250 VRMS
    Max. current 2 AAC
    Max. AC power 500 VA
    Max. load at 24 VDC 1 A

    Approvals

    EMC EN 61326-1
    LVD 2006/95/EC EN 61010-1
    EAC TR-CU 020/2011 EN 61326-1
    DNV Marine Stand. f. Certific. No. 2.4
    UL UL 508