user.png Register      arrow.png Sign in

Thailand-icon.png United-Kingdom-icon.png

4104.png

4104

Universal uni-/bipolar signal transmitter

  • Measures and outputs uni-/bipolar voltage and current signals
  • Works with both passive and active inputs and outputs
  • Uses the 4501 display for programming and process monitoring
  • Fast < 20 ms response time and excellent < 0.05% accuracy
  • Universally powered by 21.6…253 VAC / 19.2...300 VDC

Manuals : pdf-icon.png

Data sheet : pdf-icon.png

  • Overview

  • Technical details

  •  

    Application

    • Fast < 20 ms response time for measuring signals produced by torque, position, current & acceleration sensors.
    • User configurable bipolar or unipolar I/O means the 4104 is suitable for nearly any voltage or current conversion.
    • The excitation source enables measurement of two or three wire transmitters.
    • The active or passive I/O makes the 4104 perfect for power matching current loops.
    • Converts narrow bipolar inputs to wide bipolar or unipolar outputs, e.g., ±1 volt input = ±10 volt or 4...20 mA output.
    • Selectable direct or inverse I/O makes the 4104 suitable for proportional control applications.
    • The ”V-curve” function outputs 100% – 0 – 100% when a 0 – 100% input signal is present.

    Technical characteristics

    • The latest analog and digital techniques are used to obtain maximum accuracy and immunity to interference.
    • The current output can drive up to 800 Ohms, with an adjustable response time of 0.0…60.0 seconds.
    • Exceptional mA output load stability of < 0.001% of span/100 Ohm.
    • Meets the NAMUR NE21 recommendations, ensuring high accuracy in harsh EMC environments.
    • Meets the NAMUR NE43 recommendations, allowing the control system to easily detect a sensor error.
    • Each unit is tested to a high 2.3 kVAC, 3-port galvanic isolation level.
    • Excellent signal to noise ratio of > 60 dB.

    Mounting / installation / programming

    • Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
    • Approved for marine applications.
    • Programming, monitoring, and 2-point process calibration is accomplished with the 4501 detachable display.
    • All programming can be password protected.
  •  

    Environmental Conditions

    Specifications range -20°C to +60°C
    Storage temperature -20°C to +85°C
    Calibration temperature 20...28°C
    Relative humidity < 95% RH (non-cond.)
    Protection degree IP20
    Installation in Pollution degree 2 & measurement / overvoltage cat. II

    Mechanical specifications

    Dimensions (HxWxD) 109 x 23.5 x 104 mm
    Dimensions (HxWxD) w/ 4501 / 4511 109 x 23.5 x 116 / 131 mm
    Weight approx. 250 g
    Weight incl. 4501 / 4511 (approx.) 265 g / 350 g
    DIN rail type DIN EN 60715/35 mm
    Wire size 0.13...2.08 mm2AWG 26...14 stranded wire
    Screw terminal torque 0.5 Nm
    Vibration: 2...13.2 Hz ±1 mm
    Vibration: 13.2...100 Hz ±0.7 g

    Common specifications

    Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
    Max. power consumption ≤ 2.5 W
    Internal consumption ≤ 2.0 W
    Isolation voltage, test / working 2.3 kVAC / 250 VAC
    Communications interface Communication enabler 4511 / Programming front 4501
    Signal / noise ratio > 60 dB
    Response time (0...90%, 100...10%) < 20 ms
    Accuracy Better than 0.05% of selected range
    Cut-off frequency (3 dB) > 40 Hz
    EMC immunity influence < ±0.5% of span
    Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span

    Input specifications

    Current input: Signal range ±23 mA
    Current input: Programmable measurement ranges 0...20 and 4...20 mA ± 10 and ± 20 mA
    Input voltage drop 1.4 V @ 20 mA
    Loop error detection, 4...20 mA: Low < 3.6 mA
    Loop error detection, 4...20 mA: High > 21 mA
    2-wire loop supply, (terminal 43 & 44) > 16 V / 20 mA
    3-wire loop supply, (terminal 42 & 44) > 18 V / 20 mA
    Loop supply limitation, terminal 44, nom. 30 mA
    Voltage input: Signal range ±12 V
    Programmable measurement ranges, VDC 0/0.2...1, 0/1...5, 0/2...10 VDC ±1, ±5 and ±10 V
    Input resistance, voltage input > 2 MΩ

    Output specifications

    Current output: Signal range 0...23 mA (unipolar) -23...+23 mA (bipolar)
    Load stability, current output ≤ 0.001% of span / 100 Ω
    Current limit ≤ 28 mA (unipolar) ± 28 mA (bipolar)
    Programmable damping, current signals 0.0...60.0 s
    Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA
    Output limitation, on other unipolar mA signals 0 and 115% of max. value
    Output limitation, on bipolar mA signals ±115% of min. & max. values
    Current output: Active unipolar and bipolar programmable ranges 0...20 and 4...20 mA ±10 and ±20 mA
    Direct or Inverted Action
    V-curve function, active signals, 100-0-100% 20-0-20 mA
    Load (max.) 800 Ω / ±16 V @ ±20 mA
    Passive 2-wire mA output: Programmable ranges 0...20 and 4...20 mA Direct or Inverted action
    V-curve function, passive signals, 100-0-100% 20-0-20 mA
    External loop supply 3.5 - 26 V
    Programmable voltage ranges 0/0.2...1; 0/1...5 ; 0/2...10 V ±1, ±5 and ±10 V
    Direct or Inverted action
    V-curve function, voltage output, 100-0-100% 1-0-1, 5-0-5 and 10-0-10 V
    Load (min.) > 500 kΩ
    Programmable damping, voltage signals 0.0...60.0 s
    Output limitation - outside range: on unipolar V signals starting from 0 0 and 115% of max. value
    Output limitation - outside range: on unipolar V signals with offset -5% of min. value and 115% of max. value
    Output limitation - outside range: on bipolar V signals ±115% of min. & max. values
    Sensor error indication, at 4...20 mA input: selectable Low, High, Zero, None

    Approvals

    EMC EN 61326-1
    LVD 2006/95/EC EN 61010-1
    UL UL 508
    FM 3025177
    EAC TR-CU 020/2011 EN 61326-1
    DNV Marine Stand. f. Certific. No. 2.4