5337A

2-wire transmitter with HART® protocol

  • RTD, TC, Ohm, and bipolar mV input
  • 2 analogue inputs and 5 device variables with status available
  • HART® protocol revision selectable from HART® 5 or HART® 7
  • Hardware assessed for use in SIL applications
  • Mounting in Safe area or Zone 2/22

Manuals : pdf-icon.png

Data sheet : pdf-icon.png

  • Overview

  • Technical details

  •  

    Application

    • Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
    • HART® communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
    • Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
    • Amplification of bipolar mV signals to standard 4...20 mA current signals.
    • Up to 63 transmitters (HART® 7) can be connected in a multidrop communication setup.

    Technical characteristics

    • HART® protocol revision can be changed by user configuration to either HART® 5 or HART® 7 protocol.
    • The HART® 7 protocol offers:
      ∙ Long Tag numbers of up to 32 characters.
      ∙ Enhanced Burst Mode and Event notification with time stamping.
      ∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
      ∙ Process signal trend measurement with logs and summary data.
      ∙ Automatic event notification with time stamps.
      ∙ Command aggregation for higher communication efficiency.
    • 5337A is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
    • Continuous check of vital stored data.
    • Meeting the NAMUR NE21 recommendations, the 5337 HART® transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337 meets NAMUR NE43 and NE89 recommendations.

    Mounting / installation

    • For DIN form B sensor head or DIN rail mounting via the PR fitting type 8421.
    • Configuration via standard HART® communication interfaces or by PR 5909 Loop Link.
  •  

    Environmental Conditions

    Specifications range -40°C to +85°C
    Calibration temperature 20...28°C
    Relative humidity < 95% RH (non-cond.)
    Protection degree (encl./terminal) IP68 / IP00

    Mechanical specifications

    Dimensions Ø 44 x 20.2 mm
    Weight approx. 50 g
    Wire size 1 x 1.5 mm2 stranded wire
    Screw terminal torque 0.4 Nm
    Vibration IEC 60068-2-6 : 2007
    Vibration: 2...25 Hz ±1.6 mm
    Vibration: 25...100 Hz ±4 g

    Common specifications

    Supply voltage 8.0...35 VDC
    Voltage drop 8.0 VDC
    Isolation voltage, test / working 1.5 kVAC / 50 VAC
    Signal / noise ratio > 60 dB
    Communications interface Loop Link & HART®
    Response time (programmable) 1...60 s
    Accuracy Better than 0.05% of selected range
    EMC immunity influence < ±0.1% of span
    Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span

    Input specifications

    Max. offset 50% of selected max. value
    RTD input Pt50, Pt100, Pt200, Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000
    Cable resistance per wire (max.), RTD 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)
    Sensor current, RTD Nom. 0.2 mA
    TC input: Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
    Cold junction compensation (CJC) Constant, internal or external via a Pt100 or Ni100 sensor
    Voltage input: Measurement range -800...+800 mV
    Min. measurement range (span), voltage input 2.5 mV
    Input resistance, voltage input 10 MΩ

    Output specifications

    Current output: Signal range 4…20 mA
    Min. signal range 16 mA
    Updating time 440 ms
    Load resistance, current output ≤ (Vsupply - 8) / 0.023 [Ω]
    Sensor error indication, current output Programmable 3.5…23 mA
    NAMUR NE 43 Upscale/Downscale 23 mA / 3.5 mA
    HART protocol revisions HART 5 and HART 7

    Approvals

    EMC EN 61326-1
    ATEX 2004/108/EC KEMA 03ATEX1508 X
    IECEx KEM 10.0083X
    INMETRO NCC 12.0844 X
    EAC TR-CU 020/2011 EN 61326-1
    DNV Marine Stand. f. Certific. No. 2.4
    SIL Hardware assessed for use in SIL applications