6333B

2-wire programmable transmitter

  • RTD or Ohm input
  • High measurement accuracy
  • 3-wire connection
  • Can be installed in Ex zone 0
  • 1- or 2-channel version

Manuals : pdf-icon.png

Data sheet : pdf-icon.png

  • Overview

  • Technical details

  •  

    Application

    • Linearized temperature measurement with Pt100...Pt1000 or Ni100...Ni1000 sensor.
    • Conversion of linear resistance variation to a standard analog current signal, for instance from valves or Ohmic level sensors.

    Technical characteristics

    • Within a few seconds the user can program PR6333B to measure temperatures within all RTD ranges defined by the norms.
    • The RTD and resistance inputs have cable compensation for 3-wire connection.
    • A limit can be programmed on the output signal.

    Mounting / installation

    • Mounted vertically or horizontally on a DIN rail. Using the 2-channel version, up to 84 channels can be mounted per meter.
    • NB: As Ex barrier we recommend 5104B, 5114B, or 5116B.
  •  

    Environmental Conditions

    Specifications range -40°C to +60°C
    Calibration temperature 20...28°C
    Relative humidity < 95% RH (non-cond.)
    Protection degree IP20

    Mechanical specifications

    Dimensions (HxWxD) 109 x 23.5 x 104 mm
    Weight (1 / 2 channels) 145 / 185 g
    Wire size 1 x 1.5 mm2 stranded wire

    Common specifications

    Supply voltage 8.0...30 VDC
    Internal consumption 0.19...0.8 W
    Voltage drop 8.0 VDC
    Isolation voltage, ch. 1 / ch. 2 1500 VAC
    Warm-up time 5 min.
    Communications interface Loop Link
    Signal / noise ratio Min. 60 dB
    Accuracy Better than 0.1% of selected range
    Response time (programmable) 0.33...60 s
    Signal dynamics, input 19 bit
    Signal dynamics, output 16 bit
    Effect of supply voltage change < 0.005% of span / VDC

    Input specifications

    Max. offset 50% of selected max. value
    RTD input Pt100, Ni100, lin. R
    Cable resistance per wire (max.), RTD 10 Ω
    Sensor current, RTD > 0.2 mA, < 0.4 mA
    Effect of sensor cable resistance (3-wire), RTD < 0.002 Ω / Ω
    Sensor error detection, RTD Yes

    Output specifications

    Current output: Signal range 4…20 mA
    Min. signal range 16 mA
    Updating time 135 ms
    Load resistance, current output ≤ (Vsupply - 8) / 0.023 [Ω]
    Load stability, current output ≤0.01% of span / 100 Ω
    Sensor error indication, current output Programmable 3.5…23 mA
    NAMUR NE 43 Upscale/Downscale 23 mA / 3.5 mA
    *of span = of the presently selected range

    Approvals

    EMC EN 61326-1
    ATEX 2004/108/EC KEMA 09ATEX0147
    EAC Ex TR-CU 012/2011 Yes