user.png Register      arrow.png Sign in

Thailand-icon.png United-Kingdom-icon.png

6334a.png

6334A

2-wire programmable transmitter

  • TC input
  • High measurement accuracy
  • Galvanic isolation
  • Programmable sensor error value
  • 1- or 2-channel version

Manuals : pdf-icon.png

Data sheet : pdf-icon.png

  • Overview

  • Technical details

  •  

    Application

    • Linearized temperature measurement with TC sensor.
    • Amplification of bipolar mV signals to a 4...20 mA signal, optionally linearized according to a defined linearization function.

    Technical characteristics

    • Within a few seconds the user can program PR6334A to measure temperatures within all TC ranges defined by the norms.
    • Cold junction compensation (CJC) with a built-in temperature sensor.
    • A limit can be programmed on the output signal.
    • Continuous check of vital stored data for safety reasons.

    Mounting / installation

    • Mounted vertically or horizontally on a DIN rail. Using the 2-channel version up to 84 channels can be mounted per meter.
  •  

    Environmental Conditions

    Specifications range -40°C to +60°C
    Calibration temperature 20...28°C
    Relative humidity < 95% RH (non-cond.)
    Protection degree IP20

    Mechanical specifications

    Dimensions (HxWxD) 109 x 23.5 x 104 mm
    Weight (1 / 2 channels) 145 / 185 g
    Wire size 1 x 1.5 mm2 stranded wire

    Common specifications

    Supply voltage 7.2...35 VDC
    Internal consumption 0.17...0.8 W
    Voltage drop 7.2 VDC
    Isolation voltage, test / working 1.5 kVAC / 50 VAC
    Isolation voltage, ch. 1 / ch. 2 3.75 kVAC
    Warm-up time 5 min.
    Communications interface Loop Link
    Signal / noise ratio Min. 60 dB
    Response time (programmable) 1...60 s
    EEprom error check < 3.5 s
    Signal dynamics, input 18 bit
    Signal dynamics, output 16 bit
    Effect of supply voltage change < 0.005% of span / VDC
    EMC immunity influence < ±0.5% of span
    Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span

    Input specifications

    Max. offset 50% of selected max. value
    TC input: Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
    Cold junction compensation (CJC) < ±1.0°C
    Voltage input: Measurement range -12...150 mV
    Min. measurement range (span), voltage input 5 mV
    Input resistance, voltage input Nom. 10 MΩ

    Output specifications

    Current output: Signal range 4…20 mA
    Min. signal range 16 mA
    Updating time 440 ms
    Load resistance, current output ≤ (Vsupply - 7.2) / 0.023 [Ω]
    Sensor error indication, current output Programmable 3.5…23 mA
    NAMUR NE 43 Upscale/Downscale 23 mA / 3.5 mA
    *of span = of the presently selected range

    Approvals

    EMC EN 61326-1
    ATEX 2004/108/EC KEMA 10ATEX0005 X
    EAC TR-CU 020/2011 EN 61326-1